NUT UPS Server

First :

plug in ups

lsusb

should see something like this :~~ ~~

Bus 002 Device 001: ID 1d6b:0003 Linux Foundation 3.0 root hub
Bus 001 Device 019: ID 09ae:2012 Tripp Lite
Bus 001 Device 002: ID 2109:3431 VIA Labs, Inc. Hub
Bus 001 Device 001: ID 1d6b:0002 Linux Foundation 2.0 root hub
sudo apt update
sudo apt install nut nut-client nut-server

sudo nut-scanner -U

should see something like :

tripp lite

[nutdev1]
        driver = "usbhid-ups"
        port = "auto"
        vendorid = "09AE"
        productid = "2012"
        product = "Tripp Lite UPS"
        vendor = "Tripp Lite"
        bus = "001"

apc 1500

[nutdev1]
        driver = "usbhid-ups"
        port = "auto"
        vendorid = "051D"
        productid = "0002"
        product = "Back-UPS XS 1500M FW:947.d10 .D USB FW:d10"
        serial = "3xxxxxxxxxxx"
        vendor = "Tripp Lite"
        bus = "001"

apc 850

[nutdev3]
        driver = "usbhid-ups"
        port = "auto"
        vendorid = "051D"
        productid = "0002"
        product = "Back-UPS ES 850G2 FW:931.a10.D USB FW:a"
        serial = "3xxxxxxxxxxx"
        vendor = "American Power Conversion"
        bus = "001"
sudo nano /etc/nut/ups.conf
pollinterval = 1
maxretry = 3

[tripplite]
    driver = usbhid-ups
    port = auto
    desc = "Tripp Lite 1500VA SmartUPS"
    vendorid = 09ae
    productid = 2012

[apc-network]
    driver = usbhid-ups
    port = auto
    desc = "APC Back-UPS XS 1500"
    vendorid = 051d
    productid = 0002
    serial = 3xxxxxxxxx

[apc-modem]
    driver = usbhid-ups
    port = auto
    desc = "APC 850 VA"
    vendorid = 051d
    productid = 0002
    serial = 3xxxxxxxxx
sudo nano /etc/nut/upsmon.conf

``text MONITOR tripplite@localhost 1 admin secret master MONITOR apc-modem@localhost 1 admin secret master MONITOR apc-network@localhost 1 admin secret master


```bash
sudo nano /etc/nut/upsd.conf

Change 127.0.0.1

LISTEN 127.0.0.1 3493 

to all interface

LISTEN 0.0.0.0 3493 
sudo nano /etc/nut/nut.conf
MODE=netserver
sudo nano /etc/nut/upsd.users
[monuser]
  password = secret
  admin master
sudo nano /etc/udev/rules.d/99-nut-ups.rules
SUBSYSTEM!="usb", GOTO="nut-usbups_rules_end"

# TrippLite
#  e.g. TrippLite SMART1500LCD - usbhid-ups
ACTION=="add|change", SUBSYSTEM=="usb|usb_device", SUBSYSTEMS=="usb|usb_device", ATTR{idVendor}=="09ae", ATTR{idProduct}=="2012", MODE="664", GROUP="nut", RUN+="/sbin/upsdrvctl stop; /sbin/upsdrvctl start"

LABEL="nut-usbups_rules_end"
reboot (because it’s easy)

or

sudo service nut-server restart
sudo service nut-client restart
sudo systemctl restart nut-monitor
sudo upsdrvctl stop
sudo upsdrvctl start

list all usb devices

lsusb

query device by USB bus (replace with bus ID and dev ID of the UPS)

lsusb -D /dev/bus/usb/001/057

You should see something like

Device Descriptor:
  bLength                18
  bDescriptorType         1
  bcdUSB               2.00
  bDeviceClass            0
  bDeviceSubClass         0
  bDeviceProtocol         0
  bMaxPacketSize0        64
  idVendor           0x051d American Power Conversion
  idProduct          0x0002 Uninterruptible Power Supply
  bcdDevice            0.90
  iManufacturer           1
  iProduct                2
  iSerial                 3
  bNumConfigurations      1
  Configuration Descriptor:
    bLength                 9
    bDescriptorType         2
    wTotalLength       0x0022
    bNumInterfaces          1
    bConfigurationValue     1
    iConfiguration          0
    bmAttributes         0xe0
      Self Powered
      Remote Wakeup
    MaxPower                2mA
    Interface Descriptor:
      bLength                 9
      bDescriptorType         4
      bInterfaceNumber        0
      bAlternateSetting       0
      bNumEndpoints           1
      bInterfaceClass         3 Human Interface Device
      bInterfaceSubClass      0
      bInterfaceProtocol      0
      iInterface              0
        HID Device Descriptor:
          bLength                 9
          bDescriptorType        33
          bcdHID               1.00
          bCountryCode           33 US
          bNumDescriptors         1
          bDescriptorType        34 Report
          wDescriptorLength    1049
         Report Descriptors:
           ** UNAVAILABLE **
      Endpoint Descriptor:
        bLength                 7
        bDescriptorType         5
        bEndpointAddress     0x81  EP 1 IN
        bmAttributes            3
          Transfer Type            Interrupt
          Synch Type               None
          Usage Type               Data
        wMaxPacketSize     0x0008  1x 8 bytes
        bInterval             100

Webnut Docker Container

mkdir webnut
cd webnut
nano docker-compose.yml

paste contents and save

services:
  nut:
    image: teknologist/webnut
    container_name: webnut
    environment:
      - UPS_HOST=ip.address.of.nut.server
      - UPS_PORT=3493
      - UPS_USER=admin
      - UPS_PASSWORD=secret
    restart: unless-stopped
    security_opt:
      - no-new-privileges:true
    networks:
      - proxy
    ports:
      - 6543:6543
networks:
  proxy:
    external: true
docker-compose up -d --force-recreate

Linux NUT Client (remote)

sudo apt install nut-client

then verify you can connect

upsc yourupsname@ip.address.of.server
sudo nano /etc/nut/upsmon.conf
RUN_AS_USER root

MONITOR apc-modem@ip.address.of.nut.server 1 admin secret slave

MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h"
NOTIFYCMD /usr/sbin/upssched
POLLFREQ 2
POLLFREQALERT 1
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower

NOTIFYMSG ONLINE    "UPS %s on line power"
NOTIFYMSG ONBATT    "UPS %s on battery"
NOTIFYMSG LOWBATT   "UPS %s battery is low"
NOTIFYMSG FSD       "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK    "Communications with UPS %s established"
NOTIFYMSG COMMBAD   "Communications with UPS %s lost"
NOTIFYMSG SHUTDOWN  "Auto logout and shutdown proceeding"
NOTIFYMSG REPLBATT  "UPS %s battery needs to be replaced"
NOTIFYMSG NOCOMM    "UPS %s is unavailable"
NOTIFYMSG NOPARENT  "upsmon parent process died - shutdown impossible"

NOTIFYFLAG ONLINE   SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT   SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT  SYSLOG+WALL
NOTIFYFLAG FSD      SYSLOG+WALL+EXEC
NOTIFYFLAG COMMOK   SYSLOG+WALL+EXEC
NOTIFYFLAG COMMBAD  SYSLOG+WALL+EXEC
NOTIFYFLAG SHUTDOWN SYSLOG+WALL+EXEC
NOTIFYFLAG REPLBATT SYSLOG+WALL
NOTIFYFLAG NOCOMM   SYSLOG+WALL+EXEC
NOTIFYFLAG NOPARENT SYSLOG+WALL

RBWARNTIME 43200

NOCOMMWARNTIME 600

FINALDELAY 5

set net client

sudo nano /etc/nut/nut.conf
MODE=netclient

Restart service

sudo systemctl restart nut-client

check status

sudo systemctl status nut-client

Windows NUT Client

https://github.com/gawindx/WinNUT-Client/releases


Scheduling on the remote system

sudo nano /etc/nut/upssched.conf
CMDSCRIPT /etc/nut/upssched-cmd
PIPEFN /etc/nut/upssched.pipe
LOCKFN /etc/nut/upssched.lock

AT ONBATT * START-TIMER onbatt 30
AT ONLINE * CANCEL-TIMER onbatt online
AT ONBATT * START-TIMER earlyshutdown 30
AT LOWBATT * EXECUTE onbatt
AT COMMBAD * START-TIMER commbad 30
AT COMMOK * CANCEL-TIMER commbad commok
AT NOCOMM * EXECUTE commbad
AT SHUTDOWN * EXECUTE powerdown
AT SHUTDOWN * EXECUTE powerdown
sudo nano /etc/nut/upssched-cmd
``

```bash
#!/bin/sh
 case $1 in
       onbatt)
          logger -t upssched-cmd "UPS running on battery"
          ;;
       earlyshutdown)
          logger -t upssched-cmd "UPS on battery too long, early shutdown"
          /usr/sbin/upsmon -c fsd
          ;;
       shutdowncritical)
          logger -t upssched-cmd "UPS on battery critical, forced shutdown"
          /usr/sbin/upsmon -c fsd
          ;;
       upsgone)
          logger -t upssched-cmd "UPS has been gone too long, can't reach"
          ;;
       *)
          logger -t upssched-cmd "Unrecognized command: $1"
          ;;
 esac

make it executable (should already be)

chmod +x /etc/nut/upssched-cmd

Be sure PIPEFN and LOCKFN point to a folder that esists, I’ve seen it point to /etc/nut/upssched/ instead of /etc/nut If it does, create the folder or update these variables.

mkdir /etc/nut/upssched/

test

systemctl restart nut-client

then pull the plug on the ups connected to the master, check syslogs

tail /var/log/syslog